|
If you hear the FIRE ALARM:
- Do not ignore the building alarm warning
- EVACUATE. Follow evacuation plan and procedures
- Look for smoke or fire in immediate area and along exit
pathway
- Listen for instructions from: PA system, Police or Fire
Department personnel, Emergency Coordinator/Floor Wardens
- In "high-rise buildings", the fire alarm system
requires that staff on floors not directly involved in
the fire, remain in the building until instructed otherwise.
The fire alarm will sound, alerting the need to evacuate
only on the incident floor, two floors above, and one floor
below. (Does not apply to in-patient care areas
(Moffitt-Long Hospitals) and designated out-patient care
areas-See Department
Plan-Refer to the Hospital Evacuation Policy.)
- Announcements will be made on additional floors if further
evacuation is necessary. Become familiar with your building's
fire alarm and alert system. If the alarm sounds on your
floor, implement evacuation plan
Evacuation
- Never enter a smoke filled room
- Feel all doors at top for heat. Do not open door if it
is warm to touch. Even if door is cool, kneel as low to
floor as possible before opening
- Determine in advance the nearest emergency exit/route
from your work location
- Establish an alternate exit route to be used in the event
your first route is blocked or unsafe to use
- If safe to do so, and time allows, secure sensitive documents
upon exiting
- Take personal property (purse, keys, coat) with you.
You may not be allowed to re-enter the building
- Walk, do not run. Keep noise to a minimum
- DO NOT Use Elevators
- Do not push or crowd, use handrails in stairwells - stay
to the right
- Assist anyone with disabilities if they are present
- Move to your Emergency Assembly Area, and await further
instructions
- Never try to re-enter an evacuated building until authorized
personnel give the "all clear" signal
|
|
Emergency Assembly Areas (EAA) assigned to Parnassus campus
buildings are listed on the UC
Police website Click on Emergency
Preparedness Program, or call 476-5507.
EVACUATION OF DISABLED PERSONS
- It is recommended that individuals with mobility, visual
or deaf/hearing impairments (both permanent and temporary)
prepare for an emergency ahead of time by informing their
Building Management, work site Emergency Coordinators,
co-workers and classmates of the best methods of assistance
during an emergency.
- A "buddy" system should be established in which
volunteers are paired with persons with disabilities, and
will have the responsibility of alerting and assisting
them during an evacuation. Refer to:
Emergency Preparedness-Disabled Evacuation Policy
- Attempt a rescue evacuation ONLY if you have had
rescue training or the person is in immediate danger and
cannot wait for professional assistance
- All emergency exit stairwells are resistant to fire and
smoke for approximately two hours. Disabled persons are
advised to proceed to them and await assistance by rescue
personnel
- State law requires occupants
to evacuate a building when the fire alarm sounds. Title
19, Section 3.10*
- Emergency Assembly Areas (EAA) assigned to Parnassus
campus buildings are listed on the UC
Police website Click on Emergency
Preparedness Program, or call 476-5507.
|